An Experimental Study to Show the Effect of Time of Opening and Closing the Solenoid Valve on Effectiveness of Finned Cross Flow Heat Exchanger

Main Article Content

Saad S. Farhan

Abstract

In this research an experimental study was carried out to show the effect of time of
opening and closing the solenoid valve on the effectiveness of finned cross flow heat
exchanger, which has changed the time of opening and closing the solenoid valve (2, 4,
6 sec.) with change the mass flow rate of water each time and the range values between
(0.027-0.0816 kg/s) with constant of mass flow rate of air at (0.032 kg/s).
The results obtained from experiment works that the decreasing in the time of opening
and closing the solenoid valve from (6 sec.) to (2 sec.) leads to increase internal heat
transfer coefficient (hi) the highest increase was by (18.37%) at mass flow rate of water
(0.027 kg/s) and increase the overall heat transfer coefficient (U) and the highest
percentage of increase (7.36%) at mass flow rate of water (0.027 kg/s).
The experimental results obtained show that the increasing both the number of units
transmitted (NTU) and effectiveness of the finned heat exchanger when decrease the
time of opening and closing the solenoid valve from (6 sec.) to (2 sec.) and the highest
percentage of the increase occurring is (8.4%) and (1.74%) respectively at mass flow
rate of water (0.027 kg/s).

Metrics

Metrics Loading ...

Article Details

Section
Articles

Plaudit

References

Yunus A. Cengel,"Heat Transfer", Second Edition.

Baird M.H. and Taylor J.,"Heat Transfer Inpulsed Turbulent Flow", Chemical Engineering Science, Vol.21, pp. (197-199), 1966.. DOI: https://doi.org/10.1016/0009-2509(66)85010-8

علي إسماعيل، " تأثير نبضية الجريان على أداء

مبادل حراري مزدوج الأنبوب"، أطروحة

ماجستير، الجامعة التكنولوجية، 2002

H.A. Navarro and L.C. Cabezas, "Effectiveness- NTU Computation With A mathematical Model For Cross-Flow Heat Exchanger", Barazilian Journal of Chemical Engineering, Vol.24, pp.(509-521), 2007 DOI: https://doi.org/10.1590/S0104-66322007000400005

Yanhua Lu, etal., "Enhanced Performance of Heat Recovery

Ventilatory Air Flow-Induced Film Vibration (HRV Performance Enhanced By FIV)", International Journal of Thermal Sciences, 2010.

Holman J.P , “Heat Transfer”, Ninth Edition, McGraw-Hill , (2008).

Briggs D.E. and Young E.H., “Convective Heat Transfer and Press

Drop of Air Flowing Across Triangular Pitch Banks of Finned Tubes”, Fifth AICHE/ASME National Heat Transfer Conference , Houston, Texas, (1962).

Carrier W.H. and Anderson S.W., “The Resistance To Heat Flow Through Finned Tubing” , ASHVE Transitions, Vol. 50 , (1944).

Threlkeeld J. L., "Thermal Environmental Engineering", Third Edition, Prentic-Hall Inc., (1998).

Similar Articles